>>Cooling Solutions → KoldLok Raised Floor Grommets → KoldLok Extended 3" - Model #10012 → Product Details
Extended Brush - Models #10012, #10013
Applications
Installation in new or existing raised floor
tiles, designed to fill long narrow, above floor, perimeter cutouts.
Specifications
Grommet is inherently self-sealing using a multi-layer,
overlapping, and interwoven, bypass airflow closure system consisting
of:
Koldlok No. 10012 - 3"/76 mm Extended:
- Upper array of 0.010" diameter filaments
- Lower array of 0.020" diameter filaments
- Approximately 34,000 filaments
- Grommet usable cable opening size: 22" x 2 1/2"
- Grommet total cable opening size: 22" x 4 "
Grommet filaments are premium grade Nylon 6 ensuring bristle flexibility,
compliance, and self-sealing recovery. Filaments are conductive with
static dissipation properties.

Koldlok No. 10013 - 6"/152 mm Extended:
- Upper array of 0.020" diameter filaments
- Lower array of 0.036" diameter filaments
- Approximately 10,000 filaments
- Grommet usable cable opening size: 22" x 5 1/2"
- Grommet total cable opening size: 22" x 7 "

Grommet
and filaments safely bleed off any static build up on cables passing
through the cable opening caused by high velocity airflow (triboelectric
effect). Grommet is an integral part of the raised floor¹s static
dissipation system providing 1 GigaOhm of resistance.
Grommet shall achieve 100% bypass airflow sealing in areas undisturbed
by cable penetrations at static pressures up to 0.010 inches of water
column. When penetrated by four 1/2" cables, sealing is 100% effective
at the static pressure required to cool up to 3 kW/cabinet with a 95%
sealing effectiveness at a static pressure of 0.50".
Grommet ships with custom adhesive mounting kit consisting of:
- Four 3M™ 4300 series single-coated,
double-sided pressure-sensitive acrylic adhesive foam mounting tapes
- Eight 2.5mm Youngboard-C, conductive grade,
cross linked polyethylene foam buttons for ESD dissapation
Grommet is a heavy duty, 6030 aluminum alloy, anodized black with two
each 18 gauge cold rolled steel end caps. End caps are black ESD powder
coated to ensure static dissapation.
Grommet metal components are anodized to resist corrosion caused by
high humidity.
KoldLok is a permanent airflow sealing solution which will accept perpetual
cabling1 changes without requiring technician training, policing,
or labour to cut, scribe, re-install, reposition, or modify any part
of the grommet.
KoldLok is the best2 low cost solution for achieving the
hardware air intake temperature and humidity conditions required for
maximum reliability and performance by computer and communication manufacturers.
The KoldLok system of overlapping, offset, multi-layer, interwoven
bypass airflow closures utilizing KoldFilaments™ guarantees sealing
effectiveness. (U.S. Patent No. 6,632,999.)
KoldLok avoids unnecessary investments in additional cooling capacity*
by reducing bypass
airflow which increases both the effectiveness and usable capacity of
existing cooling equipment.
KoldLok's 55 - 120 (3" & 6" units) square inch usable
cable area is sufficient to accommodate virtually all cabling requirements
(typical cable fill area is less than 5 square inches, after plug has
passed through).
KoldLok addresses oversized tile cutouts and raised-floor perimeter
openings.
It is estimated that, on average, 25% of
all raised floor openings are re-cabled quarterly.
Koldlok products are compliant with Directive 2002/95/EC of the European Parliament and the Council of the Restriction of the Use of Hazardous Substances in Electrical and Electronic Equipment (RoHS).
2Filaments are premium grade Nylon 6. Filaments
made of styrene, ABS or polypropolene fall below KoldLok product standards.
*For a typical 10,000ft2 computer room with 170 cable
openings, preventing the 49,000 cubic feet per minute bypass airflow
loss through unsealed cable cutouts is equivalent to recovering the
output from five or more 20-Ton cooling units.
Background
ELIMINATE BYPASS AIRFLOW
Unsealed cable openings allow 63% or more of bypass air losses in a
typical computer room. Excessive bypass airflow will reduce underfloor
static pressure to as low as 0.01" of water column. This is much
lower than the 0.025" required for cooling high heat densities
(> 1 kW/rack or cabinet). Unmanaged bypass air results in vertical
and zone hot spots and introduces significant cooling inefficiencies.
A CLEAR SOLUTION
The KoldLok Extended Raised-Floor Grommet
automatically reseals raised-floor openings, permanently solving bypass
airflow problems.